Deviation indicating type HY-3000 / AF1
ข้อมูลสินค้า
-
รหัสสินค้า
-
แก้ไขล่าสุดเมื่อ
05/12/2016 02:55
ดาวน์โหลดไฟล์ PDF
-
รายละเอียดสินค้า
- Deviation indicating type HY-3000 / AF1
- - Simple temperature set up due to BCD S/W
- Display temperature using variation of measured value
Suffix code
Model Code Information Dimension HY-3000 96(W) X 96(H) ㎜ Deviation indicating temperature controller AF1- 48(W) X 96(H) ㎜ Control type F ON/OFF control (2 position control) P Proportional control Input K K thermocouple J J thermocouple p Resistance Temperature Detector(RTD) Pt100 Ω(IEC) V 1 - 5 V d.c C 4 - 20 ㎃ d.c Control output M Relay C Current output (4 - 20 ㎃ d.c) S S.S.R (12 V d.c voltage pulse output) Sub output(SUB)
(only with model AF1)N NONE O High action P Low action W High/Low action Control operation R Reverse action (heating control) D Direct action (cooling control) Range code Select the standard range code ※ Applied only to the AF1 Specification
[ Input ] Thermocouple K, J RTD Pt100 Ω, KPt100 Ω(139.6 Ωwhen temperature is 100 ℃) DC voltage input 1 - 5 V d.c 4 - 20 ㎃ d.c (only with AF1) Input impedance Thermocouple and DC voltage input approx. 1 ㏁ Allowable signal source resistance Thermocouple (100 Ωmax). DC voltage (2 ㏀ max) Allowable wiring resistance RTD 10 Ω max. (but resistances among 3 wires should be same) Allowable input voltage Within ±10 V (thermocouple, RTD, DC voltage). Cold junction compensation error ±2.0 ℃ (0 ~ 50 ℃) [ Performance ] Display accuracy ±2.5 % of F.S (HY-3000), ±1.0 % of F.S (AF1) Insulation resistance 20 ㏁ min (500 V d.c) Dielectric strength 2,000 V a.c 50/60 ㎐, for 1min, (between the different recharging part from each other) [ Control function and output ] Control type Proportional control, ON/OFF control (selected by composition of suffix code) Control action Reverse action or direct action (selected by composition of suffix code) Range setting Same as the input range chart Proportional band HY-3000 : ±2.5 % of F.S (Fixed), AF1 : ±3 % of F.S (Fixed) Manual reset(M.R) ±10 % of M.V (amount of output). only with Model AF1 Proportional cycle Approx. 25 ~ 30 sec (relay output), approx. 2 ~ 4 sec (S.S.R output) Hysteresis Fixed to approx. 2 % of F.S, (ON/OFF control, 400 ℃ standard) nput signal break detection When exceeding the range limit, output becomes OFF. Sub output (SUB) Only with Model AF1. High, low, high/low action (refer to suffix code) Sub output setting range Approx. 50 ℃ regarding main setting (400 ℃ range standard) Sub output hysteresis 1 ℃ fixed ● Output Control
outputRelay output Contact : 1 a, 1 b, 250 V a.c. 3 A(resistive load) (HY-3000), 5A (AF1) SSR Approx. 12 V d.c (resistive load min 800 Ω) SCR 4 - 20 ㎃ d.c. (resistive load max 600 Ω) Sub output Relay Only with Model AF1. contact : 1a, 250 V a.c. 3 A (resistive load) [ General specification ] Power Supply Voltage 110/220 V a.c 60 ㎐ Voltage fluctuation ±10 % of the power supply voltage Power consumption 3 VA max Ambient temperature 0 ~ 50 ℃ Ambient humidity 35 ~ 85 % RH (without dew condensation) Storage temperature -25 ~ 65 ℃ Vibration resistance 10 - 55 ㎐, peak amplitude 0.76 ㎜, for 1hr each in 3 axis direction Shock resistance 300 m/s² Weight 400 g (HY-3000), 350 g (AF1) [ Range and input code chart ] Code HY-3000 AF1 Input Range(℃) Input Range(℃) 1 - - Pt100 Ω -99 ~ 99 3 Pt100 Ω -50 ~ 100 - - 4 K, J, Pt100 Ω 0 ~ 100 Pt100 Ω 0 ~ 99 5 K, J, Pt100 Ω
0 ~ 200 K, Pt100 Ω 0 ~ 199 6 K, J, Pt100 Ω 0 ~ 300 K, Pt100 Ω 0 ~ 299 7 K, J, Pt100 Ω 0 ~ 400 K, Pt100 Ω 0 ~ 399 8 K 0 ~ 600 - - 9 K 0 ~ 800 - - 11 K 0 ~ 1200 - -